9 Operation
Maschinenfabrik Reinhausen GmbH 2022
131
8595028/00 EN
TAPCON
®
250
9.2.6 Monitoring settings
Monitoring U < 30 V
You can use this parameter to activate events and function monitoring. You
can select the following options:
Setting
Behavior
Activate
Monitoring is activated, even if the measured voltage
U > 30 V.
Deactivate
Monitoring is activated. Between 19 V < U < 30 V, the
following monitoring processes are suppressed:
▪ Voltage monitoring
▪ Power monitoring
▪ Power flow monitoring
▪ Function monitoring
Table 40: Activate function monitoring
9.2.7 TAPCON® 2xx retrofit
The TAPCON® 2xx retrofit function allows you to operate the device in par-
allel operation with existing devices. Parallel operation with the following ex-
isting devices is supported:
▪ TAPCON® 230 pro/expert up to year of construction 2021-08
▪ TAPCON® 240
▪ TAPCON® 250 predecessor device up to year of construction 2022-06
▪ TAPCON® 260
▪ TRAFOGUARD® with "Voltage regulation" options package