6 Mounting
Maschinenfabrik Reinhausen GmbH 2022
62
8595028/00 EN
TAPCON
®
250
6.4.5.1 Serial interface RS485
Data cable
The device is connected via the RS485 interface (COM2) via the CPU as-
sembly module (X4) or PCB connector (see Technical data).
1. Connect the RS485 interface COM-X1 on the interface module and the in-
terface CPU-X4 together using the patch cable.
2. Connect the wires of the shielded cable in accordance with the connection
diagram.
3. Position the cable shielding, screw it into the shield clamp provided, and
provide strain relief (using a cable tie).
6.4.5.2 Serial interface RS232
Data cable
The device is connected via the RS232 interface (COM2) via the CPU as-
sembly module (X5) or PCB connector (see Technical data).
1. Connect the RS232 interface COM-X1 on the interface module and the in-
terface CPU-X5 together using the patch cable.
2. Connect the wires of the shielded cable in accordance with the connection
diagram.
3. Position the cable shielding, screw it into the shield clamp provided, and
provide strain relief (using a cable tie).
6.4.5.3 Ethernet interface
► Connect Ethernet cable (RJ45 plug) to the interface CI-X1.
6.4.6 Wiring voltage measurement/current measurement UI
You must fuse the voltage measurement circuit in accordance with the con-
ductor cross section used. You can use the following fuse types:
Miniature circuit breaker
Safety fuse
Standard
IEC 60947-2
IEC 60269
Rated voltage
110/230 V (L-N)
Rated current
1.6 mA...16 A
Characteristics
B, C, K or Z
Fast-acting, medium-act-
ing or delayed-acting
Rated switching capacity
50 kA
For installation in accordance with IEC 61010-2-30
CAT II: 10 kA
Table 11: Permissible fuse types