9 Operation
Maschinenfabrik Reinhausen GmbH 2022
146
8595028/00 EN
TAPCON
®
250
▪ The same number of switching groups
▪ For parallel operation with CAN communication: Current transformers with
the same connection values must be used for all devices operating in par-
allel
9.3.3.1 Parallel operation methods
You can undertake parallel operation with various parallel operation meth-
ods.
9.3.3.1.1 Circulating reactive current minimization with CAN bus communication
With the
circulating reactive current
parallel operation method, parallel op-
eration is carried out using the circulating reactive current minimization
method.
U, I, cosφ
CAN bus
M
AVR
M
AVR
T1
T2
Figure 76: Circulating reactive current minimization with CAN bus communication
The circulating reactive current is calculated from the transformer currents
and their phase angles. The voltage regulators in the parallel operation
group share this information via CAN bus. An extra control deviation propor-
tional to circulating reactive current is added to the independently regulating
voltage regulators as a correction for the control deviation determined on the
basis of the measurement voltage. You can use the circulating reactive cur-
rent sensitivity parameter to decrease or increase this extra control devia-
tion.
The circulating reactive current method is suited to transformers connected
in parallel with a similar nominal output and short-circuit voltage U
K
and to
vector groups with the same and different step voltages. This does not re-
quire any information about the tap position.