7 Functions and settings
© Maschinenfabrik Reinhausen 2012
2117246/02 EN
TAPCON® 230 basic
87
Following the recommendation for calculating bandwidth, our example results
in:
[±B % ]
0.6
V
Step4
V
Step5
100 %
V
Nominal
[±B % ]
0.6
11275 V
11000 V
100 %
11000 V
[±B % ]
1.5 %
7.3.7.3
Setting the bandwidth
Setting range
Step size
Factory setting
0.5 % to 9 %
0.01 %
2 %
Table 18
Setting range for bandwidth
The calculated bandwidth is entered as follows:
1.
>
Control Parameters >
Vol-
tage Regulation > 4x
.
<04> Bandwidth.
2. Press
to highlight a digit.
The digit position you want is highlighted
and the value can be changed.
3. Press
to increase the value or
to
reduce it.
4. Press
.
The bandwidth is set.