7 Functions and settings
© Maschinenfabrik Reinhausen 2012
2117246/02 EN
TAPCON® 230 basic
111
7.3.13.7
Setting the Z compensation limit value
Δ
V
If Z compensation is activated, you must limit the maximum permissible in-
crease in voltage, with reference to the desired value, to avoid excessive vol-
tage on the transformer.
Setting range
Step size
Factory setting
0 %...15 %
of desired value
0.1 %
0 %
Table 29
Setting range for Z compensation limit value
Δ
V
First you have to
select the "Z" compensation method
(page 105).
To set the
Δ
V limit value for Z compensation, proceed as follows:
1.
>
Control Parameters >
Com-
pensation > 4x
.
<04> Z Comp. Limit Value.
2. Press
to increase the value or
to
reduce it.
3. Press
.
The limit value
Δ
V is set.
7.4 Configuration
This section describes all the settings for configuring system-specific data. To
make it easier for you to find specific parameters, the description refers to
subgroups of individual parameters with related functions.