7 Functions and settings
© Maschinenfabrik Reinhausen 2012
2117246/02 EN
TAPCON® 230 basic
133
7.4.2.10
Wiring and parameterizing control input/output relay
If you want to monitor the motor runtime, the voltage regulator and motor-
drive unit must be connected and parameterized as shown below.
Figure 40
Wiring for motor runtime monitoring
1
GPI "
Motor running
"
2
GPI "
Motor protective switch tripped
" (optional)
3
GPO "
Motor protective switch tripped
" (optional)
4
GPO "
Motor runtime exceeded
" (optional)
In order to be able to use the GPOs, you must wire the feedback from the
motor-drive unit "
Motor protective switch tripped
" to a GPI and parameterize
the
GPI
(see "
Assigning function to inputs (GPIs)
" on page 135). This
message resets the "
Motor runtime exceeded
" GPO when the motor protec-
tive switch is switched back on and activates the "
Motor protective switch
tripped
" message.
Setting range
Step size
Factory setting
0 s...30 s
0.1 s
0 s
Table 39
Setting range for motor runtime
To deactivate motor runtime monitoring, set the motor runtime to "0.0 s".