![MR TAPCON 230 basic Operating Instructions Manual Download Page 164](http://html.mh-extra.com/html/mr/tapcon-230-basic/tapcon-230-basic_operating-instructions-manual_1844354164.webp)
9 Technical Data
164
TAPCON® 230 basic
2117246/02 EN
© Maschinenfabrik Reinhausen 2012
9.5.2 Electromagnetic
compatibility
IEC 61000-4-2
Electrostatic discharges (ESD) 8 kV /15 kV
IEC 61000-4-3
Electromagnetic fields (HF) 20 V/m 80...3000
MHz
IEC 61000-4-4
Fast transients (burst) 6.5 kV
IEC 61000-4-5
Surge transient immunity 2 kV (outer conduc-
tor/outer conductor), 4 kV (outer conduc-
tor/ground)
IEC 61000-4-6
HF interference immunity (lines) 10 V, 150
kHz...80 MHz
IEC 61000-4-8
Power frequency magnetic field immunity 1000
A/m
IEC 61000-6-2
Immunity requirements for industrial environ-
ments
IEC 61000-6-4
Emission standard for industrial environments
Table 59
Electromagnetic compatibility
9.5.3
Environmental durability tests
DIN EN 60529
Determination of protection class for "protection
against contact, ingress of foreign objects and
water for electrical equipment" Level IP54
IEC 60068-2-1
Dry cold - 25 °C /16 hours
IEC 60068-2-2
Dry heat + 70 °C/16 hours
IEC 60068-2-3
Constant moist heat + 40 °C/93%/21 days
IEC 60068-2-30
Cyclic moist heat (12 + 12 hours)
+ 55 °C/93 % and + 25 °C/95 %/6 cycles
Table 60
Environmental durability tests