7 Functions and settings
© Maschinenfabrik Reinhausen 2012
2117246/02 EN
TAPCON® 230 basic
131
To activate or deactivate function monitoring for voltages <30 V, proceed as
follows:
1.
>
Configuration >
General >
7x
.
<07> Function Monitoring.
2. Press
or
to to activate
(ON)/deactivate (OFF) function monitoring.
3. Press
.
The function monitoring is activated/deactivated
for voltages <30 V.
Setting delay time for function monitoring
You can set the delay time after which an alarm is to be signaled.
Setting range
Step size
Factory setting
0 to 120 minutes
1 minute
15 minutes
Table 38
Setting range for function monitoring delay time
If you select "0" as the delay time, function monitoring is deactivated.
To set the delay time for function monitoring, proceed as follows:
1.
>
Configuration >
General >
8x
.
<08> Function monitoring delay.
2. Press
to increase the value or
to
reduce it.
3. Press
.
The delay time for function monitoring is set.