7 Functions and settings
© Maschinenfabrik Reinhausen 2012
2117246/02 EN
TAPCON® 230 basic
127
Figure 38
Switching pulse in standard operating mode
1
Set delay time T1
2
Start of first raise/lower switching pulse
3
Switching pulse time Ti (1.5 seconds)
4
Start of second raise/lower switching pulse
In rapid return control mode the next switching pulse can only take place after
1.5 seconds.
Figure 39
Switching pulse in rapid return control mode
1
Start of first raise/lower switching pulse
2
Set switching pulse time Ti (1.5 seconds)
3
Earliest time for the next raise/lower switching pulse (1.5 seconds)