7 Functions and settings
© Maschinenfabrik Reinhausen 2012
2117246/02 EN
TAPCON® 230 basic
121
To set the unit for the voltage display, proceed as follows:
1.
>
Configuration >
Transformer
data > 5x
.
<05> Display kV / V.
2. Press
or
to to select the kV or V
unit.
3. Press
.
The unit for the voltage display is set.
7.4.1.7
Setting current display unit
In this display, you can set the unit for the limit values displayed for overcur-
rent and undercurrent as a percentage ("%") or absolute value ("A"). The limit
values can be displayed as a percentage ("%") or absolute value ("A").
To set the unit for the current display, proceed as follows:
1.
>
Configuration >
Transformer
data > 6x
.
<06> Display % / A.
2. Press
or
to to select the % or A unit.
3. Press
.
The unit for the current display is set.