5 Mounting
© Maschinenfabrik Reinhausen 2012
2117246/02 EN
TAPCON® 230 basic
55
5.4.4
Supplying the voltage regulator using an auxiliary voltage
The device is normally supplied by the voltage transformer. If the voltage
transformer does not provide the
supply voltage and power
(see "
Technical
Data
" on page 161) needed for operation, the device must be supplied via a
88...265 V AC/DC, 50...60 Hz auxiliary supply.
NOTICE
Voltage transformer damage
Connecting an auxiliary voltage when bridges are present between the
X2:1/3 and X2:2/4 terminals can result in voltage transformer damage.
►
Remove the bridges between the X2:1/3 and X2:2/4 terminals if supplying
the device with an auxiliary voltage.
Proceed as follows to supply the device with auxiliary voltage:
1. Remove the bridges between terminals X2:1/3 and X2:2/4.
2. Connect the voltage transformer to terminals X2:1 and X2:2.
3. Connect the auxiliary voltage to terminals X2:3 and X2:4.
Figure 23
Voltage transformer and auxiliary supply connections