5 Mounting
© Maschinenfabrik Reinhausen 2012
2117246/02 EN
TAPCON® 230 basic
51
Signal lines must be routed in a shielded cable.
The individual conductors (outgoing conductors/return conductors) in the
cable core must be twisted in pairs.
The shield must be fully (360º) connected to the voltage regulator or a
nearby ground rail.
Figure 20
Recommended connection of the shielding
1
Connection of the shielding using a "pigtail"
2
Thorough connection of the shielding
NOTE
Reduced effectiveness of the shielding.
Using "pigtails" may considerably reduce the effectiveness of the
shielding.
►
Connect shield to cover all areas.
5.4.2.3
Wiring requirement in control cabinet
Note the following when wiring in the control cabinet:
The control cabinet for fitting the device must be prepared in accordance
with EMC requirements:
functional division of control cabinet (physical separation)
constant potential equalization (all metal parts are joined)
line routing in accordance with EMC requirements (separation of lines
which cause interference and those susceptible to interference)
optimum shielding (metal housing)