10. OUTPUTS
The Mobeye Argos has two outputs (O1 and O2).These relay outputs can switch external devices. The maximum
load is 2A/30V per output.
Output 1 is free to use for an external device. Switching the relay can be done in several ways: after an alarm, upon
arming, upon disarming or remote (via SMS or call).
Output 2 (O2) is configured for an external siren. This output reacts similar to the internal siren; if this is set to
‘silent’, O2 does not react. Upon a (loud) alarm, it switches for 2 minutes.
1) Replace the white grommet
with the rubber ring (using a
tool)
2) Insert the 2 wires through the hole in
to the terminal connectors (press the
orange pins):
3) Be sure the wires are
laid between the tapped
holes and the wall of the
casing before closing
the casing.
10.1 CONFIGURATION
To change the settings, please follow the instructions:
Enter your 4-digit code
(factory setting is “1111”)
Press “menu” -> light turns green
Enter the menu number (see list below)
Press “OK”
Enter the new setting
Press “OK”. The light switches off, a confirmation melody is played
In the event of an incorrect entry, the light turns red and a short beep sounds. The
menu can
be left from any position, by twice pressing “OK”.
Following settings are possible:
Menu
nr.
Description
Options
Factory setting
81
Duration of output 1
1..9999 (sec)
0
82
Duration of output 2
1..9999 (sec)
120
201…210
Authorised telephone number
Telephone number (0 to delete)
83
Behaviour output 1
1 (RC), 2 (ARMED),
3 (DISARMED),
4 (INTRUDER), 5 (TEMP)
1 (RC)
10.2 DURATION OF OUTPUTS: SWITCH OR PULSE TIMES
If an output is used, the time this output is activated can be set between 1 and 999 seconds. If the setting is set to 0,
the output does not return to its previous state automatically. An authorised number can switch it back by the SMS
command O1OFF (see 9.5). In the factory settings the duration of the pulse time for output 1 is
“0” and for output 2
“120”.