39 / 52
801314.00
•
inserted commands must be confirmed by pushing the Enter key, use the
Backspace key for correcting typing errors
•
command
help or ?
displays help with a command list
•
command
reset
resets the clock (changes are written to Flash)
•
command
conf -p
displays current parameters from setup menu
•
command
conf –n
displays current network parameters
•
command
conf -?
displays help for command conf parameters
•
example:
conf -i
192.168.0.190 sets the clock’s IP address to 192.168.0.190
•
it is necessary to end telnet connection by command
exit
Windows 7 note: The telnet is not activated in Windows 7 by default. For
activating it go to the “Control Panel” in “Start menu”, click on “Uninstall a
program (link)” in “Control Panel”, click on “Turn Windows features on or off
(link)” in “Programs and Features”, click in “Windows Features” box and find the
“Telnet Client” check box. Allow the system to install the appropriate files –
should take only a few seconds. The administrator rights are necessary for this
operation.
Hyperterminal note: The Hyperterminal application can be used as an
alternative to telnet. It is necessary to activate the “Send line ends with line
feeds” and “Echo typed characters locally” in the Properties -> Settings -> ASCII
setup window.
11.1.4 Setting network parameters over DHCPv6
IP clock mode must be set to IPv6 mode (P18: 0/2). Menu item
P25
must be set
to
3
(default setting) or
2
. The network parameters are automatically retrieved
from the DHCPv6 server.
The following DHCPv6 options can be processed:
[3] non-temporary addresses
[16] vendor class
[17] vendor options
[23] DNS servers
[24] DNS domain
[25] Identity Association for Prefix Delegation
[31] SNTP servers
The network administrator must set the DHCPv6 options on the server
accordingly.
Assigned parameters can be checked in the
P25
submenu.
11.1.5 Setting network parameters over autoconfiguration (SLAAC)
IP clock mode must be set to IPv6 mode (P18: 0/2). Menu item
P25
must be set
to
3
(default setting) or
1
.
The following SLAAC options can be processed:
[3] Prefix info
[5] MTU
[24] Route info
[25] RDNSS
The network administrator must set the SLAAC options on the server
accordingly.
Assigned parameters can be checked in the
P25
submenu