© MOBATIME
68 / 84
800847.08
9.3.6
Alarm notification
[dts4128Alarm]
Sent out if alarm status changes, i.e.
Notification
is sent out when an alarm flag is set or
deleted.
This
Notification
is always sent out, as soon as SNMP and the alarm traps are activated
and a destination address is configured.
The
Notification
sent out contains the following data:
Field
Type
Size
Description
Example
dts4128TrapAlMsgErrorNr
Byte
1 Bytes
No. of the alarm bit (0..63)
3
dts4128TrapAlMsgErrorState Byte
1 Bytes
0 = alarm bit was deleted
1 = alarm bit was set
1
dts4128TrapAlMsgErrorTime Unsigned
Int
4 Bytes
PC-time in seconds since
01.01.1970 00:00:00
946684805
dts4128TrapAlMsgErrorText Text
59 Bytes Error text
Failure supply 1