6.5.5
Time source
Time source configuration.
Path: 2 Configuration
2 Time handling
1 Time source setting1
1. Type of time source:
0=none, 1=DCF MEZ, 2=GPS-DCF (UTC), 4=NTP
2. Alarm delay at failure of time source (minutes):
0 = off, 1-2'160min, default = 0
Error: “loss of time source TO”
3. DTS stratum
0=Stratum is automatically calculated according to
the time source.
1-15=Stratum is manually set
4. Stratum limits for alarm
Limits for alarm “Time source lost“ (1-16)
Error: “loss of time source stratum”
5. Duration of stratum change 1 to 16 in the case of time loss (1-999h),
e.g. 24 hrs
stratum counts up from 1 to 16 within 24 hrs.
6. Offset per Stratum in ms (0-
40’000ms). Stratum is calculated with this value when
time is received again:
Offset/Stratum = 30ms, offset of the time source 150ms
Stratum = 5
7. Max. offset for time source to set valid time in
s at start up.
(0-
1’000’000
s)
8. Time source correction (only for DCF), +/-60'000ms
For description of time source see Chapter
DTS 4128.timeserver Moser-Baer AG
====================================
TIME SOURCE
1 Source type 2
2 Alarm delay for failure of the source 10min
3 DTS stratum (0=auto, 1-15=fix) 0
4 Stratum limit for synchalarm 12
5 Stratum TO (0-16) DCF/GPS fail 24h
6 Offset per stratum 50ms
7 Max. offset for time ok 50000us
8 Time source correction (DCF/GPS only) 0ms
98 Return and save
99 Return and discard changes