6.5.12 Alarm mask
Path: 2 Configuration
3 Alarms
1 Alarm relay
1 Alarmmask for relay
Display of all the DTS 4128 alarms (64) on 4 pages. Pages can be scrolled through with
ENTER.
An alarm on the current page can be switched on or off by entering an error number. The
page can be exited with 99. The modifications will be saved or restored one menu level
higher in “ALARM CONFIGURATION“. All Alarms with “error bitxx“ are not yet used.
A description of individual errors can be found in Appendix "C Alarm list"...
The alarm masks for the various applications (E-Mail, SNMP, SNMP Traps, alarm relay)
can differ.
The alarm masks only apply to the respective function, but not to the internal alarm
recording (menu '1. State'
'1. Alarm state' and menu '1. State'
'2. Alarm history').
DTS 4128.timeserver Moser-Baer AG
====================================
ALARMMASK Page 1
[ ]=error disabled, [*]=error enabled
[*] Bit00: DTS restart [*] Bit01: Error bit1
[*] Bit02: Supply voltage too low [*] Bit03: Error bit3
[*] Bit04: Error bit4 [*] Bit05: Error bit5
[*] Bit06: Error bit6 [*] Bit07: Error bit7
[*] Bit08: Wrong time zone DCF [*] Bit09: Error bit9
[*] Bit10: Error bit10 [*] Bit11: Error bit11
[*] Bit12: Error bit12 [*] Bit13: Error bit13
[*] Bit14: Error bit14 [*] Bit15: Error bit15
Enter alarmnumber to alter mask
Press ENTER for next part, 99 to leave>