5.10 Redundant CPU Functions Restricted in Redundant System
5.10.2 Remote Operation for Redundant System
5
- 138
1
OV
ER
VIE
W
2
SYS
TEM
CONFIGURA
TI
ON
3
TR
AC
KI
N
G
C
ABL
E
4
P
R
OCE
DURE
FO
R
S
TAR
TING
UP
A
RE
DUN
DAN
T
S
Y
S
T
E
M
5
RE
DUNDA
NT S
Y
S
T
E
M
FUNCTIONS
6
RE
DUN
DAN
T
S
Y
S
T
E
M
NE
TW
O
R
K
S
7
PR
OG
R
A
MM
IN
G
CA
UTIO
N
S
8
TR
O
U
BLE
S
HOOTING
3) Remote reset after execution of remote operation for control system or
standby system CPU module from other route
When remote operation is being performed for the control system or standby
system CPU module from GX Developer in the other route, the standby
system CPU module is not reset if remote operation is performed for the
control system CPU module.
*1
When performing remote reset for the control system or standby system CPU
module, cancel the remote operation for the standby system CPU module
from GX Developer or other means that executed the remote operation for the
standby system CPU module.
* 1: How to confirm remote operation execution
Whether remote operation has been executed or not can be checked by the special register "CPU
operation status (SD203)".
When the CPU operation status is changed by remote operation, "2 (remote operation from GX
Developer/serial communication module)" is stored into b4 to b7 of SD203.
Diagram 5.106 Remote Reset Operation after Execution of Remote STOP for Control System or Standby System CPU Module from
Other Route
Control
system
Standby
system
Control
system
Standby
system
GX Developer
GX Developer
Tracking cable
Tracking cable
RUN STOP
RUN STOP
STOP
STOP Reset STOP
Control
system
Standby
system
GX Developer
GX Developer
GX Developer
GX Developer
Tracking cable
RUN
RUN