5.6 Online Program Change for Redundancy
5.6.2 Program Change While CPU is Running
5
(4) System Switching During Online Program Change
Table5.54 shows the operation when the reason for system switching occurs during
online program change.
Yes, No
* 1: The "CAN'T SWITCH (error code: 6220)" continuation error occurs in control system CPU module
that executed the system switching instruction.
"System switching has failed due to online program change" is set in the detailed information
special relay.
* 2: The error dialog box in Diagram 5.69 will appear on the GX Developer which requested the
system switching:
(5) Waiting Time Check for Online Program Change to Standby System
The waiting time check for online program change to the standby system abnormally
completes the online program change and enables the online program change again
when a communication error occurs between GX Developer and the control system/
standby system CPU module.
When the time from when the online program change to the control system is
completed until the online program change to the standby system starts falls outside
the SD1710 setting range, this function judges it as a communication error and
abnormally completes the online program change.
SD1710 defaults to 90 seconds and can be set within the range 90 to 3600 seconds.
Table5.54 System Switching During RUN Write Redundancy Compliance Execution
Type
System Switching Condition
System Switching Execution
During RUN Write
Automatic System
Switching
Stop error
System switching request by network module
*1
System power OFF
CPU module reset
CPU module hardware malfunction
Manual System
Switching
System switching instruction
*1
System switching request from GX Developer
*2
Diagram 5.69 Error Dialog Box Displayed on GX Developer