5
- 85
5.5 Tracking Function
5.5.5 Tracking Block And Tracking Trigger
5
(c) Default Tracking Block Setting
When the tracking settings are not made (default settings), devices will be set to
tracking block No.1, based on the Default Tracking Range in Table5.44.
(d) Caution When Dividing Into Multiple Blocks
1) When tracking multiple blocks at a time, make sure that the tracking capacity is
within 100k words.
If the tracking capacity exceeds 100k words, the continuation error "TRK. SIZE
ERROR (error code: 6110) will occur and tracking cannot be performed.
2) When multiple blocks are set for tracking, they will be tracked in the setting
order starting from the one of lowest No.
Diagram 5.51 Tracking device default settings (internal device block setting)
Table 5.42 "Default Transfer Range"
is set.
X0 to X1FFF
Y0 to Y1FFF
M0 to M8191
W0 to W1FFF
Z0 to Z15