8.1 Troubleshooting Flow
8.1.5 When System Switching has Occurred
8
TROUBLESHOOTING
* 1: When using the CPU module whose first 5 digits of serial No. is "09012" or later, refer to Sections
8.1.9 and 8.1.10 for the description of error detected by the standby system after switching
systems.
Diagram 8.7 Flow for the Case where System Switching Occurred
YES
YES
YES
YES
NO
NO
NO
NO
Monitor the system switching cause using
GX Developer PLC diagnostic error
information and check for system
switching instruction arguments.Correct
abnormal behavior as appropriate for the
argument.
Confirm with the GX Developer
which performed the system
switching.
Is switch factor = 2?
1)
This is a hardware fault in the CPU
module, so please contact the nearest
Mitsubishi represenative, reseller or
branch office and explain the fault
symptoms.
Connect GX Developer to the
standby system CPU module and
check for faulty behavior using the
System Monitor / PLC
diagnostics.Correct the fault. *1
Monitor the SD1690 with GX
Developer and check the network
module that requested the system
switching.Correct the network fault.
Is switch factor = 3?
Is switch factor = 16?
Is switch factor = 17?