5
5.10 Redundant CPU Functions Restricted in Redundant System
5.10.2 Remote Operation for Redundant System
5
- 136
1
OV
ER
VIE
W
2
SYS
TEM
CONFIGURA
TI
ON
3
TR
AC
KI
N
G
C
ABL
E
4
P
R
OCE
DURE
FO
R
S
TAR
TING
UP
A
RE
DUN
DAN
T
S
Y
S
T
E
M
5
RE
DUNDA
NT S
Y
S
T
E
M
FUNCTIONS
6
RE
DUN
DAN
T
S
Y
S
T
E
M
NE
TW
O
R
K
S
7
PR
OG
R
A
MM
IN
G
CA
UTIO
N
S
8
TR
O
U
BLE
S
HOOTING
(c) Precautions when executing remote reset operation
The following describes the precautions to be taken when performing remote
reset for both systems in the backup mode.
1) Remote reset when control system CPU module is in the STOP status
and standby system CPU module is in the RUN status
System switching will occur when remote reset operation is performed for the
control system CPU module when the control system CPU module is in the
STOP status and the standby system CPU module is in the RUN status.
To disable system switching at the time of remote reset, change the operation
statuses of the control system and standby system CPU modules to the STOP
status, and then perform remote reset.
Diagram 5.104 Remote Reset Operation When Control System CPU Module Is in STOP Status and Standby System CPU Module Is
in RUN Status
Control
system
Standby
system
Control
system
Standby
system
GX Developer
GX Developer
Tracking cable
Tracking cable
STOP Reset
Reset STOP
RUN
RUN
System switching