5
- 29
5.1 Basic Concept of Redundant System
5.1.6 Start Mode
5
REDUNDANT SYSTEM FUNCTIONS
5.1.6 Start Mode
The start mode is the mode that determines device status at system startup or unreset
(RESET/L.CLR switch is set to the neutral position).
Two types of start modes are available: Initial start mode and Hot-start mode. (Initial start
mode is set by default.)
Select the start mode at backup mode settings in the redundant parameter settings of GX
Developer.
(1) Initial start mode (Default)
This mode is for clearing all devices except the file register and the latch range
settings device (word device: 0; bit device: OFF) before performing the operation.
Diagram 5.17 Operation setting Screen
Diagram 5.18 Initial Start Mode Operation
Select Initial start mode / Hot-start mode
Power the system off
and back on
System A - Control System
[Control using Initial start mode]
System B - Standby System
Tracking cable
1234
2345
D100
D101
System A - Control System
[Control using Initial start mode]
System B - Standby System
Tracking cable
0
0
D100
D101