5.5 Tracking Function
5.5.1 Tracking Function Overview
5
(4) Precautions
Tracking transfer cannot be performed in the following cases.
Scan time will shorten by the tracking transfer time.
(a) The tracking cable is disconnected or is a failure. (TRK. DISCONNECT (error
code: 6130))
Make sure the tracking cable is connected or change the cable.
(b) If the following malfunctions occur on the standby system:
• Standby system power is off
• A stop error occurs on the standby system CPU module
• The standby system CPU module is resetting
(Tracking can be performed if reset is cleared.)
When tracking device setting is not made, the program is executed with the
values before refresh at first scan after system switching.
Set the following devices as tracking devices.
• Device that makes auto refresh setting to the intelligent function module on
the extension base unit with GX Configurator
• Device that makes auto refresh setting to the CC-Link master module on the
extension base unit