5
- 41
5.3 The System Switching Function
5.3.1 System Switching Method
5
2) Reasons for system switching can be set as system switching instruction
parameter.
The system switching instruction parameter value can be confirmed in the
system switching instruction error details window, which can be displayed from
the PLC Diagnostics screen.
The system switching instruction parameter value can be used in
troubleshooting.
In addition, this parameter value is also stored in the special register SD6
(error common information) and SD1602 (system switching dedicated
instruction parameter).
(3) System Switching Priority
The system switching priorities are shown in Table5.23.
(a) System switching processing when multiple system switching requests are
issued simultaneously
When multiple system switching requests are issued simultaneously, system
switching is performed according to the priority (from high to low) of reasons for
system switching.
Diagram 5.30 Example of System Switching Instruction programming
Diagram 5.31 Error details window
Table5.23 Priority of Reasons for System Switching
Priority
Reasons for System Switching
High
Low
1
• Control system powered off
• Control system CPU module reset
2
• Stop error in control system CPU module
3
• Execution of system switching instruction
4
• System switching operation using GX Developer
5
• System switching request by network module
SP.CONTSW K1 M10
Argument (Reason for system switching, etc.)
M1000