8.1 Troubleshooting Flow
8.1.14 When "LINK PARA. ERROR" Occurs
8
TROUBLESHOOTING
8.1.14 When "LINK PARA. ERROR" Occurs
The following shows the flowchart for when "LINK PARA. ERROR" occurs during
operation of the redundant system.
Recheck the pairing settings.
Is the number of
modules set in network
parameter same with
the number of mounted
modules?
Are pairing settings
made to the Redundant
CPUs in the normal
station?
Is the network type
specified in network
parameter same
with the actual
network type?
Check the network parameter and
mounted status. If they differ, make them
to the same.
Is the refresh parameter
out of the range?
An error message [LINK PARA.
ERROR] was detected.
NO
YES
NO
NO
NO
NO
YES
Is the network
number specified in
network parameter
same with the actual
network number?
YES
Is the start I/O
number set in network
parameter same with
the actual start I/O
number?
YES
YES
YES
NO
1