8.3 Replacing Module in Redundant System
8.3.2 Power Supply Module Replacement Procedure
8
(2) Replacement Procedure
The procedure for replacing the power supply modules is shown in Diagram 8.24.
POINT
When the standby system is powered OFF, the control system CPU module
develops in a STANDBY SYS.DOWN (error code: 6300) continuation error.
After the replacement of the standby system CPU module is complete, reset
errors in the control system CPU module as necessary.
Refer to Section 8.2 for the error resetting method.
Confirming the System for the Power Supply Module to be Replaced
Confirm that the power supply module to be replaced is for the standby system (CONTROL LED
OFF).When the control system power supply module is to be replaced, switch it to the standby
system using GX Developer.
Refer to Section 5.2, for system switching using GX Developer.
Turn the Standby System Power Supply OFF
Removing the wiring
Disconnect the power supply cable from the standby system power supply module.
Replacing the Standby System Power Supply Module
1) Remove the power supply module from the main base unit
2) Mount the alternative power supply module to the main base unit.
Refer to the QCPU User's Manual (Hardware Design, Maintenance and Inspection), for
removing/mounting the power supply module.
Wiring
Connect the power supply cable to the power supply module.
Power ON the Standby System
1) Confirm that the RUN/STOP switch of the standby system CPU module is in the same position
as that of the control system CPU module.
2) Confirm that the RESET/L.CLR switch of the control system CPU module is in the center
position (reset switch neutral position).
3) Power on the control system.
Confirm the Power Supply Module's POWER LED
Confirm that the power supply module POWER LED is lit (green), and that power is being supplied
properly.
Diagram 8.24 Power Supply Module Replacement Procedure
Start
Start standby system