12 - 19 12 - 19
12 DEDICATED INSTRUCTIONS
12.5 G.INPUT
Data can be received in any user-defined message format using the nonprocedural
protocol.
Applicable device
Internal device
(System, user)
Link direct device
J \
Setting
data
Bit Word
File register
Bit Word
Intelligent function
module device
U \G
Index register
Zn
Constant Others
(S) —
—
(D1) —
—
(D2)
—
G.INPUT
(D2)
(S)
(D1)
G.INPUT
Un
Command
[Executing
condition]
[Instruction
code]
Setting data
Description
Set by
Data type
Un
Start I/O signal of the module
(00 to FE: Top two-digit when I/O signals are expressed in 3-digit.)
User BIN16-bit
(S)
Head number of the devices in which control data is stored.
User, system
(D1)
Head number of the devices in which receive data is stored.
System
Device name
Setting data
(D2)
Bit device number to be turned on at completion of execution.
System
Bit
The file register per local device and program cannot be used as the setting data.
Control data
Device
Item
Setting data
Setting range
Set by
3
(S) + 0
Receive channel
• Set receive channel
1: Channel 1 (CH1 side)
2: Channel 2 (CH2 side)
1, 2
User
(S) + 1
Reception result
• Reception result by an INPUT instruction are stored.
0: Normal
Other than 0: Error code
1
— System
(S) + 2
Receive data count
• Receive data count is stored.
2
(0 or more)
— System
(S) + 3
Allowable number of
receive data
• Set the allowable number of words for received data
that can be stored in (D1).
1 or more
User
POINT
(1) The command of G.INPUT cannot be converted into pulse.
(2) G.INPUT should be executed while the read request of the input/output signal
is turned on.
Summary of Contents for MELSEC LJ71C24
Page 1: ......
Page 2: ......
Page 18: ...A 16 A 16 INDEX REVISIONS WARRANTY...
Page 22: ...A 20 A 20 2 LJ71C24 R2 LJ71C24 R2 Before Using the Product...
Page 23: ...A 21 A 21 MEMO...
Page 38: ...4 2 4 2 4 PROCEDURES PRIOR TO OPERATION MEMO 4...
Page 105: ...7 30 7 30 7 SETTINGS FOR THE C24 MEMO...
Page 425: ......
Page 426: ......
Page 427: ......