9 - 33 9 - 33
9 DATA COMMUNICATION USING THE PREDEFINED PROTOCOL
9.5.3 Communication settings
(1) Settings on GX Works2
This section explains the settings required for executing the predefined protocol
communication on GX Works2.
For details, refer to Chapter 7.
(a) Addition of new modules and I/O assignment
For adding new modules, add an intelligent function module to a project.
For I/O assignment settings, set each module type and I/O signal range.
1) Display the "New Module" screen.
Project window [Intelligent function module] Right click [New
Module]
2) Set the following items and click the OK button.
[Display/Setting screen]
[Display/Setting details]
Item Setting
details
Module Type
Set "Serial communication module".
Module
Selection
Module Name
Set "LJ71C24".
Mounted Slot No.
Set "0".
Mount Position
Specify start XY address Set "0000".
3) Display the screen to set the I/O assignment.
Project window [Parameters] [PLC parameters] [PLC system
setting]
I/O assignment
4) Set the start I/O number to "0020", and click the End setup button.
For details of setting method for the start I/O number, refer to the
MELSEC-L CPU Module User's Manual (Function Explanation, Program
Fundamentals).
Summary of Contents for MELSEC LJ71C24
Page 1: ......
Page 2: ......
Page 18: ...A 16 A 16 INDEX REVISIONS WARRANTY...
Page 22: ...A 20 A 20 2 LJ71C24 R2 LJ71C24 R2 Before Using the Product...
Page 23: ...A 21 A 21 MEMO...
Page 38: ...4 2 4 2 4 PROCEDURES PRIOR TO OPERATION MEMO 4...
Page 105: ...7 30 7 30 7 SETTINGS FOR THE C24 MEMO...
Page 425: ......
Page 426: ......
Page 427: ......