6 - 10 6 - 10
6 SETTING AND WIRING
6.3.2 RS-422/485 cable specifications
The following shows the RS-422/485 cable specification.
(1) Use a cable that satisfies the following specification for the RS-422/485 cable
(cable to connect the C24 terminal block) within 1200m in length.
Item Description
Cable type
Shielded cable
Number of pairs
3
Conductor resistance (20
°
C)
88.0
/km or less
Insulation resistance
10000 M
- km or more
Dielectric strength
500 V DC, 1 minute
Electrostatic capacitance (1 kHz)
60nF/km or less on average
Characteristic impedance (100 kHz)
110 ± 10
Recommended conductor size
0.2 mm
2
to 0.75 mm
2
Diameter
AWG22 to AWG16
Type Stranded
Material Copper
Temperature rating
60°C or more
[Recommended cable]
SPEV (SB)-MPC-0.2 3P ..... (MITSUBISHI CABLE INDUSTRIES, Ltd.)
SPEV (SB)-0.2 3P ..... ..... ...(MITSUBISHI CABLE INDUSTRIES, Ltd.)
SPEV (SB)-0.3 3P .... ..... ....(MITSUBISHI CABLE INDUSTRIES, Ltd.)
The recommended cables above have the same electrical characteristics, but
different external diameter and internal wire colors.
(2) The total distance must be within 1200 m when two or more device are connected
in a 1:n or m:n configuration.