15 - 52 15 - 52
15 TROUBLESHOOTING
15.3.16 Communication is not available via the modem
Symptom Cause
Corrective
action
MC
Non-
procedural
protocol
Bidirectional
protocol
Predefined
• A modem initialization error occurs.
• Check the error code and execute
processing accordingly.
• Modem connection channel designation
is not performed.
• Set Modem connection channel
designation.
• Auto modem initialization
cannot be executed.
• There is an error in the switch settings in
GX Works2.
• Review the switch settings. Set it to
match the local station modem and the
TA.
• Communication protocol setting is
incorrect.
• Set the communication protocol to MC
protocol, Format 5.
• Transmission setting does not match the
external device.
• Review the transmission setting.
• Data cannot be
communicated with GX
Works2 supporting the
C24.
• Communication rate does not match the
external device.
• Review the communication rate setting.
• The product is not supported by GX
Works2.
• Confirm the GX Works2 S/W version.
• There was an error in the GX Works2
connection system.
• Check the GX Works2 connection
system.
• Set the connection system on "callback
reception waiting" and connect.
• The GX Works2 does not
receive the callback
signals from the C24.
• There is an error in the GX Works2
side’s modem settings.
• Set the modem’s settings on "Auto
Reception."
• There s an error in the GX Works2
connection system.
• Check the GX Works2 connection
system.
• Correct the C24’s settings.
• Callback connections
from GX Works2 are
refused by the C24.
• There is an error in the connection
system’s telephone No.
• Check the telephone No.
• Change the telephone No. to the data
for callback.
• There is an error in the C24 setting
value.
• Set the callback function designation on
the setting 1 to 3.
• There is an error in the GX Works2
connection system.
• Check the GX Works2 connection
system.
• Check the C24’s settings.
• When performing Auto
(callback: during fixed/
during designated
number) from GX
Works2, connection to
the C24 is refused.
• There is an error in the telephone No. of
the connection system.
• Check the telephone No.
• Change the telephone No. to the data
for callback.
• The timer value for the status of the
modem used or the line is short.
• Adjust each of the timer values for the
callback function on the GX Works2
side. (Line callback cancel wait time,
callback delay time)
• It is possible to connect
from GX Works2, but
callback from C24 cannot
be performed.
• There is a problem with the modem
specifications or settings.
• Check the modem’s specifications and
settings.
15.3.17 Communication is not available with the ISDN sub-address
Symptom Cause
Corrective
action
MC
Non-
procedural
protocol
Bidirectional
protocol
Pre-
defined
• Sub-address is incorrect.
• Review the sub-address.
• Modem does not support ISDN sub-
address.
• Use modem that supports ISDN sub-
address.
• Data cannot be
communicated with ISDN
sub-address
• Sub-address is incorrectly partitioned.
• Review how to partition the sub-address
using the TA manual.
Summary of Contents for MELSEC LJ71C24
Page 1: ......
Page 2: ......
Page 18: ...A 16 A 16 INDEX REVISIONS WARRANTY...
Page 22: ...A 20 A 20 2 LJ71C24 R2 LJ71C24 R2 Before Using the Product...
Page 23: ...A 21 A 21 MEMO...
Page 38: ...4 2 4 2 4 PROCEDURES PRIOR TO OPERATION MEMO 4...
Page 105: ...7 30 7 30 7 SETTINGS FOR THE C24 MEMO...
Page 425: ......
Page 426: ......
Page 427: ......