5 - 5 5 - 5
MELSEC-Q
5 COMMUNICATION USING GENERAL-PURPOSE INPUT/OUTPUT
The following describes the output device Y viewed from the PLC CPU when the
starting address is .
Output Device Y in the Sequence
Program
Signal Name
Value designated by
Special Variable B@
Y00 + to Y0F +
Not used
(However, it can be used as a substitute for internal relay
(M) in the sequence program)
Y10 + to Y20 +
Can be used as a general-purpose output
&H00 to &H10
Y21 + to Y28 +
Startup Program Designation
(BASIC Task No. 1 through BASIC Task No. 8)
&H11 to &H18
Y29 +
Program Startup
&H19
Y2A + to Y2F +
Cannot be used since it is used by the system.
&H1A to &H1F
Y2A+ through Y2F+ cannot be used by the user since it is used by the system. If it
used (ON/OFF) by the sequence program, its functions may not be guaranteed as an
AD51H unit.
If the head address is 60
H
, the output device numbers are
Y00+ to Y0F+
Y60 to Y6F
Y10+ to Y20+
Y70 to Y80
Y21+ to Y28+
Y81 to Y88
Y29+
Y89
Y2A+ to Y2F+
Y8A to X8F.
• Y00+ through Y0F+ • • • Not used.
(However, it can be used as a substitute for internal relay <M>)
It can be used as a substitute for internal relay (M) in the sequence program.
It cannot be communicated
with the communications
module.