11 - 237 11 - 237
MELSEC-Q
11 INSTRUCTIONS AND FUNCTIONS
Format 2 control table
%(0)
• • • • • •
Format 2 control table
• Specify 256 (&H100).
%(1)
• • • • • •
Specify the network number of the network to be accessed.
See Section 4.2.2 for the allowable specification range.
%(2)
• • • • • •
Specify the station number of the PLC CPU whose device
memory data is to be read.
See Section 4.2.2 for the allowable specification range.
%(3)
• • • • • •
Detailed error codes are stored here.
See Appendix 4.4.2 for the details about the error codes.
%(4)
• • • • • •
Processing code
• Specify 516 (&H204).
%(5)
• • • • • •
Specify the number of points for the word device (lower
digit) or bit device (higher digit) to be read. 1
%(6)
• • • • • •
Specify the number of double-word device points to be
read. 1
%(7)
• • • • • •
Fixed value
• Specify 0 (&H0).
%(8)
• • • • • •
Specify the device using the defined code.
• See Section 4.2.5 for the code numbers.
%(9)
• • • • • •
Specify the device number (lower digit) of the specified
device.
See Section 4.2.5 for the allowable specification range.
%(10)
• • • • • •
Specify the device number (higher digit) of the specified
device.
See Section 4.2.5 for the allowable specification range.
%(11)
• • • • • •
Specify the device processing unit.
• When reading in bit units
• When reading word devices
in word/double - word units
• When reading bit devices in
word units
• When reading bit devices in
double - word units
• • • •
• • • •
• • • •
• • • •
0 (&H0)
0 (&H0)
8960 (&H2300)
9984 (&H2700)
%(12)
• • • • • •
Fixed value
• Specify 0 (&H0).
1 : The number of points to be read should be within the appropriate range:
• In case of a Q series CPU
1 (number of bit device number of word device points
+ number of double - word device points) 192 points
• In case of a QnA series CPU
1 (number of bit device number of word device points
+ number of double - word device points) 96 points
Note that for ZR devices the number of points that can be read should be multiplied by 2.