57
-
3
Set the range of setting temperature in the cooling operation.
Select at desired lower and upper limit temperatures (at 1°C
intervals) with the
▲
▼
buttons.
After Selecting the desired settings, tap the Set button.
Setting upper/lower limit temp in cooling
Cool/Dry/Fan
lower limit
Back
Tap
▲▼
to set temp & tap [Set].
Menu
Set
upper limit
4
Set the range of setting temperature in the heating operation.
Select desired lower and upper limit temperatures (at 1°C intervals)
with the
▲
▼
buttons.
After selecting the desired settings, tap the Set button.
Lower limit value
Upper limit value
Cooling/Dry/Auto
16 to 28°C
30 to 35°C
Heating
10 to 22°C
22 to 30°C
■
Setting temperatures can be set in the following ranges.
Setting upper/lower limit temp in heating
Heating
lower limit
Back
Tap
▲▼
to set temp & tap [Set].
Set
upper limit
5
Select the control contents of restriction on the setting temperature
range.
①
Disable
... Restriction on the setting temperature range is disabled.
②
Enable
... The operation is restricted within the set temperature range.
③
Enable: No reflect on display
... The set temperature on the R/C can be displayed beyond the
set temperature range but actual operation is restricted within
the set temperature range.
· Over-cooling during the cooling operation or over-heating during the heating operation is not economical.
· It is recommended to set the temperature range a little higher in the cooling operation or a little lower in the heating operation.
Advice
Temp range setting Enable/Disable
Disable
Back
Select the item.
Enable
Enable : No reflect on display
PJZ012A176_EN.indd 57