80
-
'11 • KX-T-166
code
No.
Contents of data display
Data display range
Minimum
unit
Remarks
<
Control status
>
C61
Control status
0.1
(
0
:
OFF
,
1
:
ON
)
–
3-digit: Under the oil return control
2-digit: During defrosting
1-digit: Spare
C62
Control status
0.1
(
0
:
OFF
,
1
:
ON
)
–
3-digit: Under test run control
2-digit: Under the demand control
1-digit: Under the silent mode control
C63
Control status
0.1
(
0
:
OFF
,
1
:
ON
)
–
3-digit: In the capacity measuring mode
2-digit: Spare
1-digit: Spare
C64
Spare
0.1
(
0
:
OFF
,
1
:
ON
)
–
3-digit: Spare
2-digit: Spare
1-digit: Spare
C65
Protection control status
0.1
(
0
:
OFF
,
1
:
ON
)
–
3-digit: Under the HP speed reduction control
2-digit: Under the LP speed reduction control
1-digit: Under the Td speed reduction control
C66
Protection control status
0.1
(
0
:
OFF
,
1
:
ON
)
–
3-digit: Compression ratio speed reduction control
2-digit: Under the CS speed reduction control
1-digit: Under the PT speed reduction control
C67
Protection control status
0.1
(
0
:
OFF
,
1
:
ON
)
–
3-digit: Under the Tc speed reduction control
2-digit: Spare
1-digit: Spare
C68 Cause of compressor stop
0
~
127
1
See page 83
C69
Spare
0.1
(
0
:
OFF
,
1
:
ON
)
–
3-digit: Spare
2-digit: Spare
1-digit: Spare