70
-
'11 • KX-T-166
2)
Operation/ stop control by the demand input CnS2 of outdoor unit
Input: CnS2
Switching with J13
CnS2: Switching of demand control/
normal operation
Short-circuit
Open
Short-circuit (Level input) Demand control
Normal operation
Open (Pulse input)
Switching of normal operation/
demand control (Reversal)
Open
Short-circuit
Short-circuit (Level input) Normal operation
Demand control
Open (Pulse input)
NOP
Note (1) Factory setting – J13: Short-circuit, CnS2: Short-circuit (Short-circuit pin connected)
3)
The operation condition is desplayed on the LCD of remote controller and is transferred to optional centralised
controller.
4)
Demand control
Demand ratio can be switched with the dip switches (SW4-5, 4-6) on the outdoor PCB.
SW4-5, SW4-6 demand switching: 0 : Open, 1 : Short-circuit (Factory default is open)
SW4-5
SW4-6
Compressor
Out put(%)
0
0
80
1
0
60
0
1
40
1
1
0
5) CnS2 performs the following operations depending on the short circuited or open of the jumper wire (J13).
In the case of pulse input, the pulse width is 500ms or larger.
J13 – Short-circuit
ON (Short-circuit)
ON (Short-circuit)
OFF (Open)
Normal
Normal
CnS2 input
Remote controller operation
Remote controller display
Air-conditioner operation/stop OFF
OFF
OFF
Demand control
Remote
Compressor OFF
Compressor OFF
ON
ON
PUSH
PUSH
PUSH
PUSH
J13 - Open
OFF
OFF
ON
ON
Demand control
Demand control
CnS2 input
Remote controller operation
Remote controller display
Air-conditioner operation/stop
Remote
Compressor OFF
Compressor OFF
PUSH
PUSH PUSH
PUSH