108
-
'11 • KX-T-166
Error code
Remote controller:
7-segment display:
LED
Green
Red
Indoor
Outdoor
Content
E1
-
Remote controller
communication error
Keeps flashing Stays Off
Keeps flashing Stays Off
1.Applicable model
5.Troubleshooting
All models
Diagnosis
Countermeasure
Is it possible to
reset normally by the power
supply reset?
Does
the drain pump start
automatically at one
minutes after power
ON?
between indoor and outdoor
units
YES
YES
NO
Note (1) SW7-1: OFF
ON
Note (2) Does the remote controller displays “Internal check ON” even
after 3 minutes?
Reset power supply
(2)
(1)
NO
Malfunction by temporary
noise.
Check peripheral
environment
Indoor control PCB
anomaly
Replace it
Remote controller
anomaly
Replace it
2.Error detection method
When normal communication
between remote controller and
indoor unit is interrupted for
more than 2 minutes (Detectable
only with the remote controller)
3. Condition of error displayed
Same as above
4.Presumable cause
• Anomalous communication
circuit between remote
controller and indoor unit
• Noise
Note:
If the indoor unit cannot communicate normally with the remote controller for 180 seconds, the indoor unit PCB starts to
reset automatically.
Turn SW7-1 OFF.
ON
Disconnect the wire
③