110
-
'11 • KX-T-166
Error code
Remote controller:
7-segment display:
LED
Green
Red
Indoor
Outdoor
Content
E3/5
-
Outdoor unit signal line error
Keeps flashing 2 times flash
Keeps flashing Stays Off
1.Applicable model
5.Troubleshooting
All models
Diagnosis
Countermeasure
Is the power
supply to outdoor
unit OK?
~
signal wires (between
indoor
outdoor units)
connection OK?
Reset the power supply and restart.
E3 is a communication error that occurs when communication between
indoor and outdoor units is not established at all. Once the communication
between indoor and outdoor units is established, it changes to E5.
In both cases, check signal wires (between indoor
outdoor units) locally
YES
Is the
outdoor unit address
set on the indoor unit
OK?
YES
Is the LED
on indoor control
PCB OK?
YES
Is protective
fuse for the super link
circuit blown?
NO
Does E3/E5 occurs?
YES
NO
NO
NO
YES
YES
NO
NO
Temporary malfunction by
noise.
Identify the source of noise
and correct it.
Change to spare circuit.
Indoor control PCB
anomaly
Replace it
Correct it.
Correct it.
Correct it.
Outdoor control PCB
anomaly
Replace it
2.Error detection method
No outdoor unit exists in the
same superlink system.
3. Condition of error displayed
Same as above
4.Presumable cause
• Power is not supplied to the
outdoor unit
• Unmatch of pairing between
indoor and outdoor units
• Indoor control PCB anomaly
• Outdoor control PCB anomaly
• Missing local wiring
Note: