111
-
'11 • KX-T-166
Error code
Remote controller:
7-segment display:
LED
Green
Red
Indoor
Outdoor
Content
E5
-
Communication error during operation
Keeps flashing *See below
Keeps flashing 2 time flash
1.Applicable model
5.Troubleshooting
All models
Diagnosis
Countermeasure
Does
the remote controller LCD
becomes normal?
Reset the power supply and restart.
YES
NO
* In case that indoor red LED stays OFF
Is the
connection of signal wires
at the outdoor unit side
OK?
Is the
connection of signal wires
(between indoor and outdoor units)
OK?
Does the
remote controller LCD
becomes normal?
Note (1) Check the connection (disconnection, looseness)
of signal wires at outdoor terminal block
Reset the power supply and restart.
Note (2) Check the connection (disconnection, looseness,
brakage) of signal wires (between indoor and
outdoor units)
YES
NO
YES
NO
YES
NO
* In case that indoor red LED flashes 2 times
Repair signal wires.
Repair signal wires.
Go to the diagnosis of
WAIT
(1)
Unit is normal.
(Malfunction by temporary
noise, etc.)
Outdoor control PCB anomaly
(Network communicaion
circuit anomaly)
Unit is normal.
Replace it
(Malfunction by temporary
noise, etc.)
2.Error detection method
When the communication
between indoor and outdoor
units is interupted for more than
2 minutes
3. Condition of error displayed
When this anomaly is detected
during operation.
4.Presumable cause
• Unit address No. setting error
• Remote controller wires broken
• Poor connection/disconnection
of remote controller wires
• Indoor control PCB anomaly
Note:
When the pump down switch is turned on, communication between indoor and outdoor units is cancelled so that
"Communication error E5" will be displayed on the remote controller and indoor control PCB, but this is normal.