98
-
'11 • KX-T-166
Error code
Remote controller:
7-segment display:
LED
Green
Red
Indoor
Outdoor
Content
None
Louver motor anomaly
Keeps flashing Stays Off
Keeps flashing Stays Off
1.Applicable model
5.Troubleshooting
All models
Diagnosis
Countermeasure
NO
YES
Is LM harness
broken?
Is there
any disconnection
or breakage of LM
connector?
Is LM locked?
Does LM turn
smoothly?
Is there
any problem on
the connection
link?
-Check at the indoor unit side.
Is the
setting of airflow
direction change
prohibited?
Check how LS reacts
when the power is turned
OFF and ON again
Check the remote controller whether
it is fixed free flow setting.
YES
NO
Does the louver
link press LS till crick sound
can be heard?
NO
NO
YES
NO
NO
YES
In cases of FDTW, FDTS and FDTQ
Does the
louver operate when
power on?
Note (1) LM: Louver motor
(2) LS: Limit switch
YES
NO
NO
NO
NO
YES
YES
Operate after waiting for more than 1 minute.
It is normal if LM can
be stopped by pressing
LS two times.
In cases of FDT, FDTC, FDE and FDK
Check the remote controller whether
it is fixed free flow setting or not.
Correct it
Repair harness
Check connector (CNJ)
Replace Louver Motor
Correct it
Correct it
Replace indoor control
PCB
Correct it
Adjust LM lever and then
check again.
• LS anomaly
Replace
• Indoor control PCB
anomaly
Replace.
2.Error detection method
3. Condition of error displayed
4.Presumable cause
• Louver motor anomaly
• Disconnection/breakage of
LM harness
• Limit switch anomaly
Note: