64
-
'11 • KX-T-166
(4)
Outdoor fan control
(a)
Outdoor fan speed and fan motor rotation speed.
The 7th outdoor fan speed in the following table is
specified
as the rated speed. Under the normal control, the speeds up
to 8th level (800 min
−
1
) are used.
Note (1) Figures in the parentheses in the above table are applicable to FDCR224KXE6.
(b)
Fan control during cooling
During cooling and dehumidifying, fan speed is controlled in accordance with the high pressure (sensed by PSH) and the
outdoor air temperature (sensed by Tho-A).
(i)
Initial fan speeds are as follows.
Initial ourdoor fan speed at cooling
(ii)
During normal operation, the speed is changed in accordance with the high pressure value.
When it has detected HP
≧
2.2 MPa for 1 minute continuously, the fan speed is raised by one tap.
When it is 1.5 MPa < HP < 2.2 MPa, the present fan speed is maintained.
When it has detected HP
≦
1.5 MPa for 1 minute continuously, the fan speed is dropped by one tap.
Control range of fan speed is 1th – 8th speeds.
(iii)
When states under this control change from HP < 3.3 MPa to HP
≧
3.3 MPa, the fan speed is changed preferentially
to the followings. (After the change it returns to the normal control.)
When the outdoor air temperature
≧
30ºC, it changes to 7th or higher speed.
When the outdoor air temperature < 30ºC, it changes to 3rd or higher speed.
When the fan speed was higher than the above before the change of states, the fan speed is not changed.
Outdoor fan tap
Cooling
Heating
FMo1 [min
−
1
]
FMo2 [min
−
1
]
FMo1 [min
−
1
]
FMo2 [min
−
1
]
0th speed
0
0
0
0
1st speed
200
0
200
0
2nd speed
200
200
200
200
3rd speed
300
300
300
300
4th speed
400
400
400
400
5th speed
500
500
500
500
6th speed
575
575
575
575
7th speed
700
700
700
700
8th speed
800
800
800 (780)
800 (780)
Model
Outdoor air temp ≤ 10ºC
10ºC < Outdoor air Temp. < 15ºC
15ºC ≤ Outdoor air
Temp.
All models
2nd speed
4th speed
6th speed
1.5
2.2
One tap up
Maintained
One tap down
High pressure (MPa)