-
31
-
'11 • KX-T-166
Indoor unit address setting
000~127 [47]
000
000
00~31 [47]
49
49
Indoor unit address setting
00~47
49
×
00~47
49
×
00~31 [47]
49
00~31
Outdoor unit address setting
00~47
49
×
Outdoor unit address setting
●
Address No. setting
Set SW1 through 4 and SW5-2 provided on the PCB and SW1 & 2 provided on the outdoor unit PCB as shown in the drawings below.
●
Summary of address setting methods (figures in [ ] should be used with previous SL)
Do not set numbers other than those shown in the table, or an error may be generated.
Note: When units supporting new SL are added to a network using previous SL such as one involving FD A
KXE4 series units, choose previous SL for the communication protocol and set addresses manually.
Since the models FDT224 and 280 have 2 PCBs per unit, set different indoor unit No. and SW on each PCB.
●
An outdoor unit No., which is used to identify which outdoor unit and indoor units are connected in a refrigerant system, is set on outdoor unit PCB and indoor unit PCB. Give the same outdoor unit
No. to all outdoor unit and indoor units connected in same refrigerant system.
●
An indoor unit No. is used to identify individual indoor units. Assign a unique number that is not assigned to any other indoor units on the network.
Incorrect cable connection
(The signal line between outdoor units is connected to A1 and B1)
Incorrect cable connection
(The signal line between indoor unit and outdoor units is connected to A2 and B2)
Manual address setting
(previous SL/new SL)
Units supporting new SL
Units NOT supporting new SL
SW1 (SW3)
SW2 (SW4)
For ten’s place
For one’s place
By inserting a flat driver
(precision screw driver) into this
groove and turn the arrow to
point a desired number.
Indoor PCB
Outdoor PCB
SW1, 2 (blue)
SW3, 4 (green)
SW5-2
SW1, 2 (green)
For setting indoor No. (The ten’s and one’s)
For setting outdoor No. (The ten’s and one’s)
Indoor No. switch (The hundred’s Place) [OFF : 0, ON : 1]
For setting outdoor No. (The ten’s and one’s)
Automatic address setting for
multiple refrigerant systems installation
(with new SL only)
Automatic address setting for
single refrigerant system installation
(previous SL/new SL)
Indoor No. switch
Outdoor No. switch
Outdoor No. switch
Indoor No. switch
Outdoor No. switch
Outdoor No. switch
0 1
2
3
4
5
6
7
8
9
0 1
2
3
4
5
6
7
8
9
CASE 1
CASE 3
Network connector
Outdoor unit
Outdoor unit
Outdoor unit
Indoor unit
Indoor unit
Indoor unit
Indoor unit
Indoor unit
Indoor unit
CASE 4
Network connector
Outdoor unit
Outdoor unit
Outdoor unit
Indoor unit
Indoor unit
Indoor unit
Indoor unit
Indoor unit
Indoor unit
Signal line
Refrigerant pipe
Network connector
Network connector
Outdoor unit
Outdoor unit
Outdoor unit
Indoor unit
Indoor unit
Indoor unit
Indoor unit
Indoor unit
Indoor unit
Outdoor unit
Outdoor unit
Outdoor unit
Indoor unit
Indoor unit
Indoor unit
Indoor unit
Indoor unit
Indoor unit
A2·B2
A1·B1
A2·B2
A1·B1
A1·B1
A2·B2
CASE 2
●
Address setting methods
The following address setting methods can be used. The procedure for automatic address setting is different from the conventional one.
Please use the automatic address setting function after reading this manual carefully.
This control system controls the controllers of more than one air conditioner's outdoor unit, indoor unit and remote control unit through communication control, using the microcomputers built in
the respective controllers. Address setting needs to be done for both outdoor and indoor units. Turn on power in the order of the outdoor units and then the indoor units.
Use 1 minute as the rule of thumb for an interval between them.
The communication protocol can be chosen from following two types. One of them is the conventional communication protocol (previous SL) and the other is the new communication protocol (new
SL). These two communication protocols have their own features and restrictions as shown by Table 6-3. Select them according the indoor units and the centralized control to be connected.
When signal cables are connected into a network involving outdoor units, indoor units or centralized control equipment that do not support new SL, please select communications in the previous SL
mode, even if the refrigerant system is separated from theirs.
When communication is established after setting addresses, check the communication protocol with the 7 segment display panel of the outdoor unit.
※
1 Do not connect the signal line between outdoor units to A1 and B1. This may interrupt proper address setting. (Case 3)
Do not connect the signal line between indoor unit and outdoor unit to A2 and B2. This may interrupt proper address setting. (Case 4)
※
2 In Case 2, automatic address setting is not available. Set addresses manually.
Communication protocol
Address setting method
OK
※
1
×
※
2
OK
OK
OK
OK
OK
OK
OK
×
×
OK
new SL
previous SL
Automatic Manual Automatic Manual
Case 1
Case 2
When signal lines linking plural refrigerant systems are provided between outdoor units.
(When the network connector is disconnected, refrigerant systems are separated each other)
When signal lines linking plural refrigerant systems are provided between indoor units.
When only one refrigerant system is involved (signal lines do not link plural refrigerant systems)
When plural refrigerant systems
are linked with signal lines
(e.g., to implement centralized
control)
7-1. Unit address setting
7. CONTROLLER SETTINGS
×
A
B
A
B
A
B
A
B
A
B
A
B
A
B
A
B
A
B
A
B
A
B
A
B
A2·B2
A1·B1
A2·B2
A1·B1
A1·B1
A2·B2
A
B
A
B
A
B
A
B
A
B
A
B
A2·B2
A1·B1
A2·B2
A1·B1
A1·B1
A2·B2
A2·B2
A1·B1
A2·B2
A1·B1
A1·B1
A2·B2
A
B
A
B
A
B
A
B
A
B
A
B