Compressor stop cause (Cord No. C68)
It shows the latest comprressor anomalous stop cause
Compressor stop cause
No
At power on
0
Sensor disconnection
and/or short-circuit
Outdoor air temperature
1
Outdoor heat exchanger temperture 1
2
Outdoor heat exchanger temperture 2
3
Discharge pipe temperature sensor 1(CM1)
4
Suction pipe temperature sensor
5
Sub-cooling temperature sensor 1(liquid side)
6
Sub-cooling temperature sensor 2(gas side)
7
Under-dome temperature sensor 1
8
Power transistor temperature sensor 1
9
Active filter temperature sensor
10
High pressure sensor
11
Low pressure sensor
12
Anomaly detection
HP anomaly
20
LP anomaly
21
Td1 anomaly
22
FMo1 anomaly
23
FMo2 anomaly
24
Inverter 1 current cut
25
Inverter 1 startup failure
26
Inverter 1 communication error
27
Inverter 1 anomalous compressor induced voltage and torque
28
Inverter 1 power tansistor overheat
29
Inverter 1 rotor lock
30
Liquid flooding anomaly
31
Stop by restriction
Outdoor operation mode heating/cooling switching
40
Heating overload protection
41
Stopping time by compressor dilution ratio protection control (Less than 30 minutes) *3
Stopping time by compressor dilution ratio protection control (Over 30 minutes) *3
50
51
*3 As the actual operation, write the stop factor 50 at the start of power supply and, when the accumulated compressor start inhibition
time (counted only when the remote controller is turned on) has exceeded 30 minutes, overwrite on it with the stop factor with
51. The code of this stop factor is retained even after the protective start inhibition has been released, until it is overwritten with
another stop factor.