103
-
'11 • KX-T-166
Error code
Remote controller:
7-segment display:
LED
Green
Red
Indoor
Outdoor
Content
WAIT
WAIT
(3)
Keeps flashing Stays Off
Keeps flashing Keeps flashing
1.Applicable model
5.Troubleshooting
All models
(No display on the remote
controller after power ON)
Diagnosis
Countermeasure
NO
NO
NO
NO
NO
NO
NO
NO
YES
YES
YES
YES
YES
YES
YES
YES
No display on the remote
controller after power ON
Does
indoor green LED keep
flashing?
Does
outdoor red LED flash
2-times?
Is
the connecting wires
between indoor and outdoor
units comnnected
properly?
Is
AC380-415V detected
between L1-L2, L2-L3,
L3-L1 respectively at outdoor
terminal block?
Is
AC220-240V detected
between L-N at indoor
teminal block?
Is
The fuse on indoor control
PCB OK?
Is
AC18V or higher is
detected between Red-
Red at secondary side of
indoor transformer? (1)
Is
DC10-11V between
X-Y at indoor control PCB
side when removing
remote controller ?
Note (1) except FDT
and FDTC
Fuse blown
Replace fuse
Transformer anomaly
Remote controller wire
short-circuited
Remote controller anomaly
Indoor control PCB
anomaly
Remote controller anomaly
Brakage of connecting
wires of remote controller
Correct the connecting
wires properly
Outdoor control PCB
anomaly
Replace it
Breakage of connecting
wire Noise
Indoor control PCB
anomaly
Replace it
2.Error detection method
3. Condition of error displayed
4.Presumable cause
• Fuse blown
• Noise filter anomaly
• Anomalous connection of
wire between PCBs
• Indoor control PCB anomaly
• Remote controller anomaly
• Breakage of connecting wires
of remote controller
• Outdoor control PCB anomaly
Note: