78
-
'11 • KX-T-166
(b) List of 7-segment displays
Code
No.
Contents of display
Data display range Minimum unit
Remarks
Error
display [Exx]
Caution
display [Axx]
Special
display [PdS][PdE][CH][CHF][CO][HE][PCL][dLP][dLC][dLH][oPE][CAP]
Code
No.
Contents of data display
Data display range Minimum unit
Remarks
<Sensor value, actuator information>
C00
CM1 operation frequency
0 ~ 130
1Hz
C01
(Spare)
C02
Tho-A Outdoor air temperature
L,-20 ~ 43
1°C
C03
Tho-R1 Heat exchanger temperature 1
L,-25 ~ 73
1°C
C04
Tho-R2 Heat exchanger temperature 2
L,-25 ~ 73
1°C
C05
(Spare)
C06
(Spare)
C07
Tho-D1 Discharge pipe temperature (CM1)
L,31 ~ 136
1°C
C08
(Spare)
C09
(Spare)
C10
Tho-C1 Under-dome temperature (CM1)
L,5 ~ 90
1°C
C11
(Spare)
C12
Tho-P1 Power transistor temperature (CM1)
L,5 ~ 136
1°C
C13
(Spare)
C14
Tho-SC Sub-cooling coil temperature 1
L,18 ~ 73
1°C
C15
Tho-H Sub-cooling coil temperature 2
L,-25 ~ 73
1°C
C16
Tho-S Suction pipe temperature
L,-25 ~ 73
1°C
C17
Inverter secondary current
0 ~ 50
1A
C18
CT1 (CM1) current
0 ~ 50
1A
C19
(Spare)
C20
EEVH1 Heating expansion valve opening angle
0 ~ 500
1 pulse
C21
(Spare)
C22
EEVSC Sub-cooling coil expansion valve
opening angle
0 ~ 500
1 pulse
C23
FMo1 Actual fan speed
0 ~ 999
10min-1
C24
FMo2 Actual fan speed
0 ~ 999
10min-1
C25
PSH High pressure sensor
0 ~ 4.15
0.01MPa
C26
PSL Low pressure sensor
0 ~ 1.70
0.01MPa
C27
(Spare)
C28
(Spare)
C29
(Spare)
C30
Pressure switch
0,1
(0: Open, 1: Close)
–
Order of 100: 63H1-1
Order of 10: (Spare)
Order of 1: (Spare)
C31
External input
0,1
(0: Open, 1: Close)
–
Order of 100: CNS1
Order of 10: CNS2
Order of 1: CNG1