232
APPX
Appendix 2 Remote Register
Details of remote registers
Error code
■
Device number
■
Description
The error code is stored. (
When multiple errors have occurred, these errors are stored in the error code (RWr1) in the following priority.
• When the error type differs, they are stored in the order of major error > moderate error > minor error.
• When the error type is the same, the error that occurred later is stored.
■
Method for clearing an error
The method for clearing an error depends on the error type.
Name
Device number
Error code
RWr1
Error type
Clearing an error
Major error
The error cannot be cleared.
Moderate error
Eliminate the error cause, and power off and on the I/O module. Or, turn on and off Error clear request flag
(RWw0.b10).
Minor error
Eliminate the error cause, and power off and on the I/O module. Or, turn on and off Error clear request flag
(RWw0.b10).