166
8 FUNCTIONS
8.3 CC-Link IE TSN Network Synchronous Communication Function
Input time acquisition control
The time when an input has changed can be acquired by using the input time acquisition control. Select a type of input
change (rising edge or falling edge) to be acquired by setting ON/OFF selection flag (RWw4, RWw5).
Set a type of input change (rising edge or falling edge) for ON/OFF selection flag (RWw4, RWw5).
The I/O module sends the following information to the master station, at the third synchronization cycle from the detection
of input change set in ON/OFF selection flag (RWw4, RWw5).
• Input time information X
(RWr10 to RWr8F): Time when the input change has been detected
• Input ON/OFF information (RWr4, RWr5): The type of input change (rising edge or falling edge) that has been detected at
the synchronization cycle same as the time stored in Input time information X
(RWr10 to RWr8F)
ON/OFF selection flag X0: The falling edge is set.
The falling edge has been detected at 20:00, July 24th, 2020.
Input time information X0: 20:00, 7/24/2020, Input ON/OFF information X0: Falling edge
(1) Synchronization cycle
(2) Input
(3) Operation
(4) Output
(5) Falling edge is monitored.
ON
OFF
OFF
Ö
Õ
Ó
Ô
Ò
(2) (3) (4)
(2) (3) (4)
(2) (3) (4)
(2) (3) (4)
(2) (3) (4)
(2) (3) (4)
(2) (3) (4)
(1)
(5)
Scan program
Synchronization
control interrupt
program
External input X0
(Status of the X0
terminal)
I/O module
Monitoring input
change by the I/O
module
Summary of Contents for NZ2GN2B1-32D
Page 2: ......
Page 112: ...110 4 PROCEDURES BEFORE OPERATION MEMO ...
Page 193: ...10 MAINTENANCE AND INSPECTION 191 10 MEMO ...
Page 263: ...I 261 MEMO ...
Page 267: ......