236
APPX
Appendix 2 Remote Register
Output Y ON information
■
Device number
■
Description
Whether output Y has been turned on or not can be checked with Output Y ON information Y
(RWrC, RWrD).
When the synchronization output timing setting control or the output time setting control (CC-Link IE TSN
Network synchronous communication function) is used, whether output Y has been turned on or not can be
checked with Output Y ON information Y
(RWrC, RWrD).
■
Output Y ON information Y0 to YF (RWrC)
■
Output Y ON information Y10 to Y1F (RWrD)
Output Y ON information Y
(RWrC, RWrD) can be cleared using Output Y ON information clear request Y
(RWwC,
RWwD).
While Output Y ON information clear request is turned on, regardless of the remote output signal status,
output Y ON information continues to be cleared.
Name
Device number
Output Y ON information
RWrC, RWrD
b15
b14
b13
b12
b11
b10
b9
b8
b7
b6
b5
b4
b3
b2
b1
b0
YF
YE
YD
YC
YB
YA
Y9
Y8
Y7
Y6
Y5
Y4
Y3
Y2
Y1
Y0
Off: Output Y has never been turned on.
On: Output Y has been turned on.
b15
b14
b13
b12
b11
b10
b9
b8
b7
b6
b5
b4
b3
b2
b1
b0
Y1F
Y1E
Y1D
Y1C
Y1B
Y1A
Y19
Y18
Y17
Y16
Y15
Y14
Y13
Y12
Y11
Y10
Off: Output Y has never been turned on.
On: Output Y has been turned on.
Performed by I/O module
Executed by the program
(1) Remains on even after Y0 turns off.
(2) Turns off when the clear request turns on.
OFF
OFF
ON
ON
ON
OFF
ON
OFF
ON
OFF
(1)
OFF
OFF
OFF
OFF
OFF
(2)
External output signal Y0
Output Y current value Y0
(RWrA. b0)
Output Y ON information Y0
(RWrC.b0)
Output Y ON information
clear request Y0 (RWwC.b0)