6 INSTALLATION AND WIRING
6.3 Installation Environment and Installation Position
123
6
Installation position
I/O module (except for waterproof module)
When installing the I/O module (except for waterproof module) in a control panel, provide a clearance of 60mm or more (1)
between the module and the sides of the control panel or other parts to ensure good ventilation and facilitate module change.
When installing two or more CC-Link IE TSN remote modules next to each other, they can be installed in contact with each
other.
I/O module (waterproof module)
When installing the I/O module (waterproof module) in a control panel, provide a clearance of 50mm or more (1) between the
module and the sides of the control panel or other parts to ensure good ventilation and facilitate module change.
When installing two or more CC-Link IE TSN remote modules next to each other, they can be installed in contact with each
other.
When using a right-angle, waterproof connector or a Y-branch connector, however, provide a clearance to avoid stress on
cables.