8 FUNCTIONS
8.3 CC-Link IE TSN Network Synchronous Communication Function
173
8
Setting of the CC-Link IE Field Network synchronous communication function
The CC-Link IE TSN Network synchronous communication function of the I/O module is set with the network configuration
setting.
Operating procedure
1.
Open the "CC-Link IE TSN Configuration" window.
2.
Select the module in "Module List" and drag and drop it to the list of stations or the network map.
3.
Set "Network Synchronous Communication" to "Synchronous".
4.
Click the [Close with Reflecting the Setting] button to complete the setting process and close the window.
To use the CC-Link IE TSN Network synchronous communication function for the I/O module, enable the CC-
Link IE TSN Network synchronous communication function of the master station.
For details, refer to the following.
User's manual for the master station used
Precautions
• If "Network Synchronous Communication" is set to "Synchronous" for an I/O module not supporting the CC-Link IE TSN
Network synchronous communication function, a network synchronous communication setting error (error code: D020H)
occurs in the I/O module or the event code of 00C71 is registered with event history of the master station.
• When setting "Network Synchronous Communication" to "Asynchronous", set the synchronous X/Y control mode (factory
default) as the operation mode. If "Network Synchronous Communication" is set to "Asynchronous" for the I/O module
whose operation mode is the synchronization cycle timing control mode or the set time synchronization control mode, a
synchronous communication settings inconsistent (error code: 010BH) occurs.